Ok I'll take a stab at this.
VT ratio of 700 means that you are reading 1/700 of the actual voltage.
CT ratio of 200 means you are reading 1/200 of the actual current
V = (700)117 = 81900V
A = 200(2.5) = 500A
VA=81900 x 500 VA = 40950 kVA
\(kWatts = PF \times kVA = 0.89 \times 40950 ~kVA = 36445.5~ kWatts\\ kVAR = \sqrt{1-PF^2} \times kVA = 0.46 40950 ~kVA = 18671.6~ kVAR\)
.